Startseite ASF-Leckanzeiger Gardner Denver Thomas GmbH

    
    
Deutsch/German Polska/Polish
Leak Detection Systems Overview
Operating Principles of Leak Detection Systems
Container Design
Piping
Liquid / Gas Medium
Accessories
Downloads
   ASF Leak Detector Type D29 - Pressure Principle

   General Design Permit (DIBT) No. Z-65.26-410 (Tested by TÜV Nord, Hamburg)


Print Version




 
Application
 
  • The leak detector is used to monitor non-pressurized underground/aboveground double-walled pipelines.
  • For monitoring of water-polluting liquids, and flammable liquids having a flash point of < 55°C.
  • The interstitial space of the double-walled pipeline must be suited for the connection and operation of this leak detector.
  • The leak detector can be used for monitoring of several underground pipelines utilizing a manifold.

The leak detector must be mounted outside the hazardous area (ex-zone)!


Function
 
  • Leak detector according to the principle of positive pressure with integrated pump and pressure relief.
  • The outside air is sucked through a vessel with dry beads (air dryer), which dries the air down to a relative humidity of <10%.
  • The saturation of the dry beads, depending on the humidity, is reached in about 12-15 months, identifiable by the color change, - initially orange - colorless at saturation.

Switching Values:
Alarm On PAE = 1,1 bar
Pump Off PPA = 1,5 bar

Overpressure Protection
Pressure relief valve of the pump opens at
PSV = 1,65 bar

For further data please see the data sheet of the D29 leak detector.
 

Operating Conditions
 
  • The double-walled pipelines must be depressurized.
  • Leak detection fluid may not be present in the interstitial space of the container.
  • Appropriate manifolds together with a D29 leak detector may only be used for monitoring underground pipelines.


Accessories
 
  • Installation of a potential free relay.
  • Installation in protective casing with exterior alarm and heating.
  • Mounting kits for connection to pipelines and manifolds.


Dryer / Drying Beads

LTR
By default, with V = 180 cm³

Selection of the air dryer for aboveground applications can be found in the technical description.
 

Mounting Examples

Please click on the picture for a larger view!

Picture a Picture b

 
Product Images

Leak Detector Type D29 - Pressure
Leak Detector Type D29 - Pressure

Documentation
 
Installation and Operation Manual D29Installation and Operation Manual D29
Data Sheet D29Data Sheet D29
General Design Permit (DIBT) D29General Design Permit (DIBT) D29
D29 AccessoriesD29 Accessories & Assembly Kits




Top

Print Version

Copyright 2008-2015 © Gardner Denver Thomas.
Terms of Use/Privacy Policy | Imprint | General Terms and Conditions